Interfaces for PROFINET and PROFIBUS DP communication are integrated in the SIMATIC Drive Controller. The following communication options are available for your automation task:
列表: SIMATIC Drive Controller communication options
Communication option | PN | DP |
---|---|---|
PG communication for commissioning, testing and diagnostics | X | X |
HMI communication for operator control and monitoring | X | X |
Data exchange with TCP/IP, UDP, ISO-on-TCP, ISO protocol | X | - |
Data exchange via OPC UA as server | X | - |
Data exchange via OPC UA as client | X | - |
Direct data exchange between IO controllers | X | - |
Communication via Modbus TCP | X | - |
Communication via UDP Multicast | X | - |
Sending process messages via e-mail | X | - |
S7 communication | X | X |
S7 routing | X | X |
Web server of the CPU Data exchange via HTTP(S), for example for diagnostics | X | - |
SNMP (Simple Network Management Protocol) | X | - |
Time-of-day synchronization | X | X |
Coupling with the clock pulse system of the technology I/Os X142 and with SINAMICS Integrated | X | - |
The SIMATIC Drive Controller also has two USB interfaces 3.0. These do not currently have an assigned function.
Communication between CPU and SINAMICS Integrated is based on PROFIdrive mechanisms. The communication services used for this are based on PROFIBUS DP and are processed over an internal, high-performance interface that allows cycle times as low as 250 μs.